SafetyBUS 100 - 120 Ohm | 2003717 | 2003717
BUS | FIELDBUS cables for industrial & process automation

SafetyBUS 100 - 120 Ohm

03.10.07.01

|

Use of Cable

as fieldbus cables for SafetyBUS systems for fixed installation & flexible applications, in the field of factory automation.

SafetyBUS is a safe, open fieldbus system, which is optimized for the transmission of data relating to machine safety: timing and content consistency of the data have the highest priority here.

 

Product variants
Product information "SafetyBUS 100 - 120 Ohm"
Special features
  • largely resistant to grease, coolant fluids and lubricants
  • oil-resistant: acc.to DIN EN 60811-2-1 (only mineral oil)
  • EMC compliant shielding
  • max. cable lengths for a bus segment at stated transmission rate:
             50 kbit/s-max.1,0km | 125 kbit/s-max.500m | 250 kbit/s-max.250 m |
             0,5Mbit/s-max.100m
Remarks
  • conform to RoHS
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • FC-Type = 'fast-connect' construction
Conductor material: Bare copper strand
Conductor class: 19-wired
Core insulation: Foamed polyolefin
Core identification: White, brown, green
Stranding: Cores stranded in layers
Inner sheath material: PVC
Shield3: Copper braid tinned
Outer sheath: PVC
Sheath colour: Yellow RAL 1003 (YE)
Outer diameter: 8,0 mm
Rated voltage: 250 V (not for high voltage purposes)
Testing voltage: 1,5 kV
Loop resistance: Max. 26,0 Ω / km
Capacity: Nom. 45nF/km
Characteristic impedance: 100 - 120 Ω
Min. bending radius fixed: 8 x d
Min. bending radius moved: 10 x d
Operat. temp. fixed min/max: -40 °C / +80 °C
Operat. temp. moved min/max: -10 °C / +70 °C
Burning behavior: Flame-retardant acc. to IEC 60332-1-2, Cable Flame Test (UL 2556)
Approvals: UL/CSA - cURus 300 V, 80 °C
Copper weight: 50,0 kg/km
Weight: 87,0 kg/km

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
ASi-BUS Aktor Sensor Interface 03.10.06.01
BUS | FIELDBUS cables for industrial & process automation
for fixed installation & limited flexible applications, UL/CSA
Item count 10
PROFIBUS DP / FMS / FIP 150 Ohm - HF 03.10.01.02
BUS | FIELDBUS cables for industrial & process automation
for high flexible applications (drag chain, robotic & festoon) UL/CSA
Item count 12