Electronic and control cables for intrinsically safe circuits
PAARTRONIC®-CY LIYCY (TP) EB
02.03.06
|
Use of Cable
exclusively for use in self-protective circuits, as impulse and data transmission cable, control and connecting cable in process controlled facilities in measurement and control technology for lossless data and signal transmission. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.
Product information "PAARTRONIC®-CY LIYCY (TP) EB"
Special features
- twisted pairs
- for intrinsically safe electric circuits
- protection class "i" acc. to VDE 0165
- largely resistant to acids, bases and specified types of oil
- intrinsically safe systems are circuits where no spark and no thermic effect in normal operation or in failure can ignite explosive surrounding areas. These products are intended for use within <50 V AC resp. <75 V DC voltage. Therefore they are not subject to the EU Low Voltage Directive.
- conform to RoHS
- free from lacquer damaging substances and silicone (during production)
- recommended for EMC-applications
- also available: ÖPVC-JZ-YCY EB, ELITRONIC®-CY EB (DIN47100)
Conductor material: | Bare copper strand |
---|---|
Conductor class: | Acc. to IEC 60228 cl. 5 |
Core insulation: | PVC |
Core identification: | Acc. to DIN 47100 different colours |
Stranding: | 2 cores twisted to a pair, pairs stranded in layers |
Shield3: | Copper braid tinned; coverage approx. 85% |
Outer sheath: | PVC |
Sheath colour: | Blue, RAL 5015 |
Rated voltage: | Uo/U: 300/500 V (see special features) |
Testing voltage: | Core/core: 1,5 kV; core/shield: 2 kV |
Conductor resistance: | Acc. to IEC 60228 cl. 5 |
Insulation resistance: | Min. 20 MΩ x km |
Current-carrying-capacity: | Acc. to DIN VDE, s. Techn. Guidelines |
Capacity: | Core/core ca. 120 nF/km; core/shield ca. 160 nF/km |
Min. bending radius fixed: | Up to 12 mm Ø 5 x d; > 12 mm Ø 7,5 x d |
Min. bending radius moved: | Up to 12 mm Ø 10 x d; up to 20 mm Ø 15 x d; > 20 mm Ø 20 x d |
Operat. temp. fixed min/max: | -30 °C / +80 °C |
Operat. temp. moved min/max: | -5 °C / +70 °C |
Burning behavior: | Self-extinguishing & flame-retardant acc.to IEC 60332-1 |
Standard: | Similar to DIN VDE 0812 |
There aren't any asked questions yet.
ELITRONIC®-OZ-CY LIYCY-OZ EB
02.03.02
Electronic and control cables for intrinsically safe circuits
300/500V, shielded, blue
300/500V, shielded, blue
Item count
33
PAARTRONIC®-CY LIYCY (TP) EB
02.03.06
Electronic and control cables for intrinsically safe circuits
DIN47100, 250V, shielded, twisted pairs, blue
DIN47100, 250V, shielded, twisted pairs, blue
Item count
34