PAARTRONIC®-CY-CY LIYCY-CY (TP) | 0500682 | 0500682
Electronic cables

PAARTRONIC®-CY-CY LIYCY-CY (TP)

02.01.05

|

Use of Cable

data transmission cable, control and connecting cable predominantly for transmission of analog and digital signals in process controlled facilities in measurement and control technology for lossless transmission of data and signals. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.

Product variants
Product information "PAARTRONIC®-CY-CY LIYCY-CY (TP)"
Special features
  • single shielded pairs with contact protection by special PVC-insulation
  • twisted pairs
  • largely resistant to acids, bases and specified types of oil
  • free from lacquer damaging substances and silicone (during production)
  • recommended for EMC-applications
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
Remarks
  • conform to RoHS
  • also available:
    ELITRONIC®-CY-CY LIYCY-CY (with single shielded cores)
    PAARTRONIC®-DY-CY LIYDY-CY(with spiral copper shield)
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: Bare copper strand
Conductor class: Acc. to IEC 60228 cl. 5; exception: 0,34 mm², stranded (7 x 0,25 mm)
Core insulation: PVC
Core identification: Acc. to DIN 47100 different colours
Stranding: 2 cores twisted to a pair; shielded pairs with sheath stranded in layers
Shield: Copper braidpair-shild tinned; coverage approx. 85%
Inner sheath material: PVC pair-sheathing over braid
Shield3: Copper braid tinned; coverage appr ox. 85%
Outer sheath: PVC
Sheath colour: Grey, RAL 7032
Rated voltage: 250 V; peak-voltage on 0,14 mm²: 350 V; > 0,14 mm²: 500 V
Testing voltage: On 0,14 mm² core/core: 1,2 kV; core/shield: 2kV > 0,14 mm²: core/core: 1,5 kV; core/shield: 2kV
Conductor resistance: Acc. to IEC 60228 cl. 5
Insulation resistance: Min. 20 MΩ x km
Current-carrying-capacity: Acc. to DIN VDE, s. Techn. Guidelines
Capacity: Core/core ca. 120 nF/km; core/shield ca. 160 nF/km
Min. bending radius fixed: Up to 12 mm Ø: 5 x d; up to 20 mm Ø: 7,5 x d; > 20 mm Ø: 10 x d
Min. bending radius moved: Up to 12 mm Ø: 10 x d; up to 20 mm Ø: 15 x d; > 20 mm Ø: 20 x d
Operat. temp. fixed min/max: -30 °C / +80 °C
Operat. temp. moved min/max: -5 °C / +70 °C
Burning behavior: Self-extinguishing & flame-retardant acc.to IEC 60332-1
Standard: Similar to DIN VDE 0812

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
ELITRONIC®-CY LIYCY, ELITRONIC® LIYCY 02.01.02
Electronic cables
DIN47100, 250V, shielded, CPR Eca
Item count 209
PAARTRONIC®-CY LIYCY (TP) 02.01.04
Electronic cables
DIN47100, 250V, twisted pairs, shielded, CPR Eca
Item count 89