Power Cables
NYCY 0,6/1kV
09.07.02
|
Use of Cable
power cable for use in generating plants, industrial facilities, switching stations, in local networks and power supply industry. Use predominantly for laying underground, indoor- and outdoor use, cable channels and in water when increased mechanical protection resp. contact protection in case of failure is required.
Product information "NYCY 0,6/1kV"
Special features
- 0,6/1 kV operating voltage, 4 kV testing voltage
- UV-resistant
- no hood termination necessary when laying in dry rooms
- use of concentric conductor as shield, neutral conductor or earth conductor is permitted but not as outer conductor
- free from lacquer damaging substances and silicone (during production)
- conform to RoHS
- conform to 2006/95/EC-Guideline CE
- with blue outer sheath for intrinsically safe facilities available upon request
- We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: | Bare copper conductor |
---|---|
Conductor class: | Acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1 |
Core insulation: | PVC |
Core identification: | Single core black; multi core acc. to VDE 0207 part 4 |
Stranding: | Multi core stranded in layers |
Inner sheath material: | Filler sheath |
Shield3: | Concentric conductor of blank round copper wires |
Outer sheath: | PVC |
Sheath colour: | Black |
Rated voltage: | Uo/U: 0,6/1 kV |
Testing voltage: | 4 kV |
Conductor resistance: | At +20 °C acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1 |
Current-carrying-capacity: | Acc. to DIN VDE, see Technical Guidelines |
Min. bending radius fixed: | Single core: 15 x d ; multi core: 12 x d |
Operat. temp. fixed min/max: | -40 °C / +70 °C |
Operat. temp. moved min/max: | - 5 °C / +50 °C |
Temp. at conductor: | + 70 °C in operation; +160 °C in case of short-circuit |
Burning behavior: | Acc. to VDE 0472-804-B and IEC 60332-1 |
Standard: | Acc. to DIN VDE 0276-603 and IEC 60502 |
Approvals: | VDE |