NYCWY 0,6/1kV | 4000303 | 4000303
Power Cables

NYCWY 0,6/1kV

09.07.03

|

Use of Cable

power cable for use in generating plants, industrial facilities, switching stations, in local networks and power supply industry. Use predominantly for laying underground, indoor-and outdoor-use, cable channels and in water when increased mechanical protection resp. contact protection in case of failure is required.

Product variants
Product information "NYCWY 0,6/1kV"
Special features
  • 0,6/1 kV operating voltage 4 kV testing voltage
  • UV-resistant
  • no hood termination necessary when laying in dry rooms
  • use of concentric undulated CEANDER copper conductor as shield, neutral conductor or earth conductor is permitted but not as outer conductor
  • any branch connection possible because of non-engraving of concentric CEANDER conductor (CW)
  • free from lacquer damaging substances and silicone (during production)
Remarks
  • conform to RoHS
  • conform to 2006/95/EC-Guideline CE
  • with blue outer sheath for intrinsically safe facilities and also as NAYCWY (with aluminium conductors) available upon request
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: Bare copper conductor
Conductor class: Acc. to DIN VDE 0295 class 1 or 2 resp. IEC 60228 class 1 or 2
Core insulation: PVC
Core identification: Acc. to VDE 0293-308
Stranding: Cores stranded in layers
Inner sheath material: Filler sheath
Shield3: Concentric conductor of blank round copper-wires ceander form
Outer sheath: PVC
Sheath colour: Black
Rated voltage: Uo/U: 0,6/1 kV
Testing voltage: 4 kV
Conductor resistance: At +20 °C acc. to DIN VDE 0295 class 1 oder 2 resp. IEC 60228 class 1 or 2
Current-carrying-capacity: Acc. to DIN VDE, see Technical Guidelines
Min. bending radius fixed: Single core: 15 x d ; multi core: 12 x d
Operat. temp. fixed min/max: -40 °C / +70 °C
Operat. temp. moved min/max: - 5 °C / +50 °C
Temp. at conductor: + 70 °C in operation; +160 °C in case of short-circuit
Burning behavior: Acc. to VDE 0472-804-B and IEC 60332-1
Standard: Acc. to DIN VDE 0276-603 and IEC 60502
Approvals: VDE

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
NYCY 0,6/1kV 09.07.02
Power Cables
0,6/1kV, shielded, UV-resistant, direct burial, VDE, CPR Eca
Item count 47
NYY 0,6/1kV 09.07.01
Power Cables
0,6/1kV, UV-resistant, direct burial, VDE, CPR Eca
Item count 179