NHXMH | 5001004 | 5001004
Halogen-free installation cables

NHXMH

09.06.01

|

Use of Cable

installation cable with improved burning behaviour for use in fire vulnerable areas and areas with high concentration of people and property values for fixed laying on-wall and in-wall, in dry, humid and wet rooms, in brickwork and concrete exceptional in cast, vibrated or rammed concrete.

Product variants
Product information "NHXMH"
Special features
  • halogen-free cable with minimal production of smoke
  • no corrosive or toxic gas
  • free from lacquer damaging substances and silicone (during production)
Remarks
  • conform to RoHS
  • conform to 2006/95/EC-Guideline CE.
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: Bare copper conductor
Conductor class: Acc. to DIN VDE 0295 class 1 or 2 resp. IEC 60228 class 1 or 2
Core insulation: Cross-linked polymer
Core identification: Acc. to VDE 0293-308
Stranding: Cores stranded in layers
Inner sheath material: Halogen-free filler sheath
Outer sheath: Halogen-free special compound
Sheath colour: Grey
Rated voltage: Uo/U: 300/500 V
Testing voltage: 2 kV
Conductor resistance: At +20 °C acc. to DIN VDE 0295 class 1 or 2 resp. IEC 60228 class 1 or 2
Current-carrying-capacity: Acc. to DIN VDE, see Technical Guidelines
Min. bending radius fixed: 4 x d
Operat. temp. fixed min/max: -30 °C / +70 °C
Operat. temp. moved min/max: - 5 °C / +50 °C
Temp. at conductor: + 70 °C in operation; +250 °C in case of short-circuit
Burning behavior: Acc. to VDE E 0482-332-10 and IEC 60332-3 smoke tightness acc. to DIN VDE 0472 part 816 test C and IEC 61034-1 corrodibility acc. to VDE 0472 part 813
Standard: Acc. to DIN VDE 0250 part 214
Approvals: VDE

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
NHXMH 09.06.01
Halogen-free installation cables
300/500V, CPR Dca
Item count 84