MULTIBUS & INTERBUS 100 - 120 Ohm - HF | 2003672 | 2003672
BUS | FIELDBUS cables for industrial & process automation

MULTIBUS & INTERBUS 100 - 120 Ohm - HF

03.10.02.02

|

Use of Cable

MULTIBUS - as fieldbus cable for use in a variety of fieldbus systems such as DIN measuring bus, BITBUS (IEEE 1118), Local Operating Network (LON) SUCOnet P, Modulink-P, P-VariNet, FIP ...
   and
INTERBUS - as remote bus cable (Type RBC) or installation remote bus with integrated power supply (type INBC) in the field of production automation, for high flexible applications (e.g. power chains, gantry robots, pick and place units, conveyors, machine tools, automated production systems, etc.)

Product variants
Product information "MULTIBUS & INTERBUS 100 - 120 Ohm - HF"
Special features
  • low adhesion
  • largely resistant to lubricants, coolants fluids and grease
  • oil-resistant: acc. to DIN EN 60811-2-1
  • UV-resistant
  • EMC compliant shielding
  • max. cable lengths for a bus segment acc.to PI at stated transmission rate:
         MULTIBUS: 93,75kbit/s-max.1,2km | 187,5kbit/s-max.1km | 0,5Mbit/s-max.400m
                             1,5 Mbit/s-max.200m | 12,0 Mbit/s-max.100m
         INTERBUS: 0,5Mbit/s-max.400m
Remarks
  • conform to RoHS
  • conform to DESINA (violet)
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • FRNC: Flame Retardant Non Corrosive, halogen free
Conductor material: Bare copper strand
Conductor class: Super fine wired acc. to IEC 60228 cl. 6
Core insulation: BUScores: Polyolefine, supply cores: PVC
Core identification: BUScores: acc. to DIN 47100, supply cores: rd, bu, gnye
Stranding: BUScores stranded to a pair
Overall stranding: (INBC) BUSelem. a. supply cores stranded
Shield3: Copper braid tinned
Outer sheath: PUR
Sheath colour: Violet RAL 4001 (VT)
Rated voltage: BUScores: 250 V (not for high voltage purposee); supply cores: 500 V
Testing voltage: 1,5 kV
Loop resistance: Max. 159,8 Ω/km - 0,25 mm²: max. 39,0 Ω/km 1,0 mm²
Capacity: Max. 60 nF/km
Characteristic impedance: MULTIBUS: 100 - 120 Ω; INTERBUS: 100 Ω +/- 15 Ω
Min. bending radius fixed: 5 x d
Min. bending radius moved: 7,5 x d < 3mTL* | 15 x d ≥ 3mTL*,
Operat. temp. fixed min/max: - 40 °C / +80 °C
Operat. temp. moved min/max: - 30 °C / +70 °C
Halogen free: Acc. to IEC 60754-1 (FRNC Typen)
Burning behavior: Flame retardant acc. to IEC 60332-1-2; CMX: acc. to IEC 60332-1-2, VW-1
Resistant to oil: Acc. to DIN EN 60811-2-1
Approvals: UL/CSA - cULus 300V, 75°C, CMX/SunRes/OilRes
Speed: Self-supporting: 4 m/s
Acceleration: Max. 5 m/s²
Bending cycles: Up to 7,5 Mio.

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
ASi-BUS Aktor Sensor Interface 03.10.06.01
BUS | FIELDBUS cables for industrial & process automation
for fixed installation & limited flexible applications, UL/CSA
Item count 10
PROFIBUS DP / FMS / FIP 150 Ohm - HF 03.10.01.02
BUS | FIELDBUS cables for industrial & process automation
for high flexible applications (drag chain, robotic & festoon) UL/CSA
Item count 12