INDULINE® RE-2X(St)YSWAY-fl | 2001345 | 2001345
Instrumentation cables

INDULINE® RE-2X(St)YSWAY-fl

02.08.05.01

|

Use of Cable

Instrumentationcable for optimal, lossless transmission of analogous and digital signals in measurement and process control technology. Suitable for intrinsically safe systems zone 1 and zone 2 group II classified areas acc. IEC 60079-14. Suitable for dry and humid rooms as well as outdoor use and laying underground.

Product variants
Product information "INDULINE® RE-2X(St)YSWAY-fl"
Special features
  • more steady at higher frequencies and temperatures (+90°C) by XLPE core insulation (cross-linked PE)
  • high crosstalk and low cable attenuation
  • largely resistant to acids, bases and usual oils; Standard EN 50288-7
  • protection for high mech. requirements and magnetic shield (galvanized round or flat steel-wires, additional inner sheath)
  • oil resistance: ICEA S-73-532 / NEMA WC 57-2004 § 6.9.3
  • Sunlight resitance: UL 1581 Section 1200
  • flame-retardant acc. IEC 60332-1-2 and IEC 60332-3-24 (Cat. C)
Remarks
  • conform to RoHS; conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • suitable for intrinsically safe systems zone 1+2 group II acc. IEC 60079-14
  • we are pleased to produce special versions e.g. fire-resistant (Mica), halogen-free, oil- and chemical-resistant (lead sheath or GuardSheath - unleaded), BS 5308, MESC etc. >> also available as compensation cable > INDUTHERM <<
Conductor material: Bare copper strand
Conductor class: 7-wired construction acc. to IEC 60228 cl. 2
Core insulation: XLPE (cross-linked polyethylene)
Core identification: Pairs pairs: single-coloured with numerals: core A: black, core B: white; triple: single-coloured, core A: white, core B: red, core C: black, core A and C with numerals
Stranding: Pairs stranded in layers
Inner sheath material: PVC, black
Shield3: Galvanized round or flat steel-wires (SWA)
Outer sheath: PVC
Sheath colour: Black or blue RAL 5015 for intrinsically safe systems
Rated voltage: 300 V
Testing voltage: Core/core (AC/DC): 1.5 / 2 kV (duration 1 minute)
Conductor resistance: 0.5mm²: max.36.7 Ω/km; 0.75mm²: max.25.0 Ω/km; 1.3mm²: max.14.2 Ω/km
Insulation resistance: Min. 5 GΩ x km
Current-carrying-capacity: Acc. to DIN VDE, s. Techn. Guidelines
Capacity: Max.115 nF/km
Inductivity: Ca. 1 mH/km
Coupling: Max. 500 pF/500 m
Min. bending radius fixed: 10 x d
Operat. temp. fixed min/max: -40°C / +70°C
Operat. temp. moved min/max: -5°C / +50°C
Burning behavior: Self-extinguishing and flame-retardant acc. to IEC 60332-1-2 and IEC 60332-3-24 (Cat. C)
Resistant to oil: ICEA S-73-532 / NEMA WC 57-2004 § 6.9.3

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
INDULINE® RE-2X(St)Yv-fl 02.08.01.01
Instrumentation cables
300V, shielded, EN50288-7, CPR Eca
Item count 104
INDULINE® RE-2X(St)YSWBY-fl PiMF 02.08.04.01
Instrumentation cables
300V, shielded, pairs in metal foil, steel wire braid, EN50288-7, CPR Eca
Item count 35