ELITRONIC®-CY LIYCY UL/CSA | 0503802 | 0503802
Approved electronic and data cables

ELITRONIC®-CY LIYCY UL/CSA

02.04.02

|

Use of Cable
UL/CSA approved data transmission cable, control and connecting cable predominantly for transmission of analog and digital signals in process controlled facilities in measurement and control technology for lossless data and signal transmission. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.
Product variants
Product information "ELITRONIC®-CY LIYCY UL/CSA"
Special features
  • largely resistant to acids, bases and specified types of oil
  • LABS-/silicone-free (during production)
  • recommended for EMC-applications
  • capable for soldering, crimp and cut-and-clamp
Remarks
  • conform to RoHS
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: Copper strand tinned
Conductor class: 7 resp. 19 wires
Core insulation: PVC
Core identification: Acc. to DIN 47100 with grey outer sheath acc. to IC colour-code with black outer sheath
Stranding: Stranded in layers
Shield3: Copper braid tinned; coverage approx. 85%
Outer sheath: PVC
Sheath colour: Grey or black
Rated voltage: 300 V
Testing voltage: Core/core: 2.0 kV; core/shield: 1.5 kV
Conductor resistance: Acc. to IEC 60228 cl. 2
Insulation resistance: Min. 20 MΩ x km bei 20 °C
Current-carrying-capacity: Acc. to DIN VDE, s. Techn. Guidelines
Capacity: Core/core ca. 120 nF/Km; core/shield ca. 160 nF/km
Min. bending radius fixed: 7,5 x d
Min. bending radius moved: 15 x d
Operat. temp. fixed min/max: -30 °C / +80 °C
Operat. temp. moved min/max: -5 °C / +80 °C
Burning behavior: Self-extinguishing & flame-retardant acc.to IEC 60332-1
Standard: UL style 1061, UL style 2464 and CSA AWM I/II A
Approvals: UL/CSA: 80 °C - 300 V

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
DATATRONIC®-CY UL/CSA 02.04.05
Approved electronic and data cables
DIN47100, 250V, 300V, shielded, twisted pairs, UL/CSA, AWG
Item count 21
ELITRONIC®-CY LIYCY UL/CSA 02.04.02
Approved electronic and data cables
DIN47100 or IEC, 300V, shielded, UL/CSA
Item count 102